Home  Site Map  Source Page

The Air House Engine Test Facility

Diagram and description of the control panel


“The air control diagram as seen by the plant controller. The control buttons are next to the valves operated.”


“The control room and switch rooms are in an annexe along the side of the Compressor House, with the control room centrally situated and overlooking the engine-room floor. The 33 kV switchgear is in two separate rooms, one on each side of the control room. The battery room and medium voltage and 11 kV switchgear are also in this annexe. The 33 kV switches are single busbar 600 ampére rating, vertically-isolated oil immersed with a rupturing capacity of 750 MVA. Bus section switches divide the sets into groups of two and are also 1,200 ampére rating. Site services are taken from an 11kV ring main fed from a10 MVA transformer at each end.

In addition to the electrical panels, the control room also contains the air desks, one to each set, and a complete air mains diagram for the test area. The sets, having been put on to the governor gear, are synchronised and completely controlled from this desk. Fault indications are received here of excess bearing temperature, cooling water failure, stator temperature, etc. It is important to maintain the air supply to the test cells, and for this reason automatic shut-down is restricted to major mechanical or electrical faults, which have been found to be, of themselves, the prime cause of shut-down.”

MVA=Megavolt Ampére



Top